T-COILHeat Exchanger for Exhaust Heat Recovery (T-COIL)

T-coil Q&A

Please refer to the folloing frequently asked questions about T-coil

Q1.What kind of terms need providing SDAT with to consider introducing a T-coil?

A

I would like you to show the temperature and flow rate of Spply and Exaust air so that we could desing a T-coil.

Q2.How can T-coil's temperature efficiency be culculated?

A

T-coil's temperature efficiency show that what percentage in temperarture gap between supply and exhaust air causes exhaust gas temp rise. The cluculatoion fomula is as follows:.

Q3.How high can efficiency of T-coil be at the most?

A

Efficiency of T-coil can be over 70%, but actually we provide a lot of customers with T-coils that have btween 50 to 60% efficiency considering the spaces installed and cost-benefit performance.

Q4.What is maxmum exhaust temperature that T-coil could recover heat from ?

A

T-coil can recover heat from between about 380 to 400℃ air that Boiler and Petrochemical plant exhast . For more information,please contact us.

Q5.How can we mesure the flow rate?

A

Generally speaking, you should mesure some poins after you make some holes in the duct and put a probe of an anemometer into the hole.

Q6.How can recovered heat be calculated?

A

Q = Vs × γs × Cps × (T2-T1) × 60 ÷ 3.6

Q :Recovered heat(W) *1W=3.6KJ
Vs :Flow rate of supply air(low temperature fluid)(Nm3/min)
γs :Specific gravity of supply air(low temperature fluid)(kg/Nm3) *When supply is dry : γs=1.293kg/Nm3
Cps:Specific heat of supply air (low temperature fluid) (at inlet and outlet side average temperature) (kJ / kg ℃)
T1 : Supply air (low temperature fluid) inlet side temperature (℃)
T2 : Supply air (low temperature fluid) outlet side temperature (℃)

Temperature (℃) 0 20 40 60 80
Specific heat 1.0046 1.0046 1.0088 1.0088 1.0088

Q7.How can T-coil be installed?

A

T-coil has 3 ways (Vertical way ,Horizontal way and Up and down way) to be installed , though the way needed to be chosen in advance.

  • Vertical way
  • Horizontal way
  • Up and Down way

Q8.Does T-coil need maintanance to be used?

A

T-coil doesn't need maintanance to be used excapt that Dust that the air includes have to be washed.

Q9.If exhast air includes some dust,waht mesures do you have?

A

In order to remove dust of the air, you might want to set a filter ahead of T-coil.
In addition, T-coil can be equipped with inspection windows so that the heat transfer surface can be efficiently washed away by high-pressure washing machine etc.,.

Q10.What measures do you have against the drainage from T-coil?

A

T-coil can be epuipped with drainage pipes so that the drainage can go away.

Q11.How can the efficiency of T-coil be measured?

A

Once you can measure the flow rate and temperature of supply and exhast air, you can assess the efficiency of T-coil. in addition, you can assess the efficiency according to confirming whether fuel is used less or not.

Q12.Are there any caustions, when T-coil is disposed of?

A

There is possibility that some T-coils contain Flourocarbons. Please contact us before you dispose one.

We provide sustainable heat recovery

SDAT Co., LTD Tokyo Branch

SDAT製品のご相談・
お問い合わせ
お問い合わせフォーム
サーモコイルのご相談・
お問い合わせ
TEL.03-4363-1028TEL TOKYO
TEL.06-6695-3384TEL OSAKA
お問い合わせフォームMAIL

MENUCLOSE